Modern designed tools and equipment in the hands of qualified, experienced men, produce a high quality product. Modular design and factory assembly mean lower cost, and the larger the unit, the more significant the savings.

Technolog SA
MINIMUM SPACE
The modular designed Apin boiler is very compact and requires a minimum of space. Space is also saved when the control panel is factory installed.

HIGH STEAM QUALITY
The Apin Steam drum is sized to match the size of the unit. Each APIN Boiler is equipped with the appropriate steam internals for your application. Stable water level results in drier steam.

HIGH EFFICIENCY
Complete waterwall membrane construction means less heat loss to the atmosphere and pressurized firing allows for better excess air control. Completely sealed combustion chamber with the appropriate expansion joints to prevent combustion leakage.

JACKETING
All APIN Boilers are Stainless Steel SA 304 jacketed for no paint or maintenance.

MINIMUM MAINTENANCE
The Apin Boilers require very little upkeep with no baffles, hand holes to maintain. Since it is membrane sealed, no insulation or outer casing burn-out. Tube radius permits ease of tube cleaning. Rapid circulation keeps sludge and scale deposits to a minimum.

SAFETY AND COMBUSTION CONTROL SYSTEM
Apin designs and provides a flame failure safety controls system to suit all burner arrangements and satisfy insurance code requirements.

FACTORY INSTALLED BURNERS WITH CONTROLS
Many other package steam generators cannot be factory-checked because the burner is not made by the manufacturer. APIN designs, manufactures and install the Burner and Steam Generator and assumes full responsibility for the entire generator-burner control package. Apin Can also install and test fired well-known Burners from other Burner manufactures.

SINGLE RESPONSIBILITY

Apin designs and manufactures every modular components in the steam generator, burner, economizer, air heater, super-heater, heat recovery units so as to ensure entire customer satisfaction.

SOLID FOUNDATION
APIN was founded in 1946 and since that time , we have systematically built a highly motivated staff of experienced personnel. Our staff has in excess of 300 years of Boiler experience. This experience has been invaluable in completing 700+ Boilers in the 800 HP and above sizes.

PRODUCT FLEXIBILITY
APIN has designed and built boilers in “O” , “D” and “A” types , firing all types of fuels , Heat Exchangers , Economizers , Oil Heaters and other equipment related to the Heat Transfer Industry.

TECHNOLOGY
APIN has invested in an extensive computer library of process and mechanical design programs. These programs coupled with our experienced staff , enable APIN to offer innovative and competitive designs for all types of applications, as well as model existing designs. Use of these programs ensures quality of design , which is the first step in a fully functional Quality Assurance Program.

POLICY
Maintain and upgrade the methods required to provide a product that meets or exceeds the client’s needs, Maintain continued contact with the client to assure their confidence in our ability to provide the required quality during engineering , procurement , fabrication and shipment. Maintain a reporting system within the company to provide the confidence to APIN management that the intended quality is achieved and APIN´s Manager of Engineering is in responsible charge for our QA policy and execution.
Maintain a Q.A. Department to verify that the vendor , as a standard practice, is providing a product that meets/exceeds the client’s technical specifications, and the Quality level required.

SUMMARY
We realize that APIN cannot be all things to all clients , nor are all clients compatible with APIN´s corporate strategy. We also understand that we cannot achieve the level of quality and service that we seek to achieve if we only sell products based on low price. It is with this in mind , that we have sought to align ourselves with major clients , that place a high value on good service , high quality products , and strong technical expertise.

Watertube Boiler

APIN D English SPECS

Boiler Model

 

AC - 300/4

AC - 500/5

AC - 700/6

AC - 900/8

AC -1200/11

AC -1500/12

Steam Capacity , Lbs/Hr

PPH

10,000

17,000

20,000

30,000

40,000

50,000

Furnace Heat Absorption*

Btu/Hr/Ft2

25,776

29,823

33,913

35,682

37,233

38,515

Total Surface

Ft2

1,593

1,740

2,109

2,470

3,714

3,945

Furnace Volume

Ft3

254

283

334

436

728

770

        

Boiler Dimensions

 

 

 

 

 

 

 

Width

inches

93

110

120

120

136

132

Height

inches

116

136

146

150

150

168

Length

inches

186

211

246

300

334

312

Steam Drum Diameter

inches

24

30

36

36

42

42

Water Drum Diameter

inches

12

24

24

24

24

24

Boiler Tubes

 

 

ASTM A 178 - A , 2" O.D. X 0.105"wall

 

Stack Diameter

inches

20

24

24

30

36

38

Furnace Manhole

inches

20" I.D.

 

 

 

 

 

        

Casing & Insulation

 

 

 

 

 

 

 

Outer Casing

All STAINLESS STEEL , SA 304

Insulation

1000°F Mineral Wool

        

Connections

 

 

 

 

 

 

 

Steam Outlet

inches

4

4

6

6

6

6

Safety Valves

inches

Number of Valves according to ASME CODE

 

 

Feedwater

inches

1.5

1.5

1.5

1.5

2

2

Water Column

inches

1.25

1.25

1.25

1.25

1.25

1.25

Vent

inches

1

1

1

1

1

1

Chemical Feed

inches

1

1

1

1

1

1

        

Weights

 

 

 

 

 

 

 

Shipping Weight

lbs

26,500

39,500

46,500

53,500

61,000

62,500

Operating Weight

lbs

31,00

46,000

53,000

61,000

69,000

71,000

        

Design Pressure Standard : 200 psig with water inlet from and at 212°F.     Optional Pressures to 600 psig and 750°FTT

Fuels : Natural & LPG , #2 & #6 oil

THERMAL OIL HEATER Sto 200 Million Btu/Hr,

* Based on Natural Gas firing